48v inverter output short circuit and output voltage protection instructions

Column:Industry News Time:2021-10-19
When the inverter output feedback does not have a zero-crossing point for 64ms continuously,

(1) Output short-circuit protection of the inverter

When the inverter output feedback does not have a zero-crossing point for 64ms continuously, it is regarded as an output short circuit, the UPS output is turned off, the UPS beeps for a long time and an alarm is displayed on the panel.

(2) Output voltage protection of the inverter

When the inverter output feedback voltage is lower than 140V or higher than 276V for 80ms continuously, it is regarded as output undervoltage or overvoltage for protection, the UPS transfers to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(3) BUS overvoltage protection of the inverter

When the BUS voltage exceeds 440V for 64ms continuously, it is considered that the BUS is over-voltage and protected, the UPS transfers to the bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(4) Inverter current limiting protection

The protection circuit monitors the output current value. If it exceeds 3.6 times the rated current, the current-limiting protection circuit immediately turns off the PWM and resets the PWM at a 19.2kHz cycle until the output current value is less than 3.6 times the rated current.

(5) Over-temperature protection of the inverter

When the system temperature is too high, the temperature switch trips, making the UPS transfer to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel (detection time 0.5s).

(6) Load protection of inverter


110%~130%

If the UPS detects that the load exceeds 110% before jumping from the bypass to the inverter, it cannot enter the inverter state. At this time, the UPS beeps once every 0.5s and displays the status on the panel. If the load is detected between 110% and 130% after power-on, the UPS will beep once every 0.5s and display the status on the panel. After 10s, the UPS will switch to bypass mode; after that, if the load is reduced to below 100%, the UPS Restart the soft boot. If the UPS detects that the load is between 110% and 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; if the load is not reduced below 100%, the UPS will transfer to bypass after 10s Mode, this state can only be released by pressing the OFF button.


Greater than 130%

If the load is detected to be greater than 130% after power-on, the UPS will beep once every 0.5s, and the status will be displayed on the panel, and the UPS will transfer to the bypass state. After that, if the load is reduced to below 100%, the UPS restarts. If the UPS detects that the load is greater than 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; at the same time, the UPS will switch to bypass mode; this status can only be released by pressing the OFF button.


日本免码va在线看免费| 国产精品人妻4p一区| 国产精品一区二区久久| 欧美日韩精品一区丁香| 国产精品一区二区久久hs| 日本午夜福利在线视频| 中文字幕日韩欧美推理片免费观看| 日韩精品一区二区亚洲v欧美v日韩| 漫画韩漫画免费在线观看| 91香蕉频蕉app下载| 九色精品国产亚洲av麻豆一| 亚洲国产精品午夜在线| 2018在线不卡爱视频| 呻吟丰满一区二区三区| 中文字幕熟女一区二区三区| 色综合久久久久综合激情| 国产精品不卡a∨在线观看| 韩国爱情电影年轻的母亲| 成人亚洲视频在线观看| 欧美日韩一区二区中文字幕| 亚洲人妻最新中文AV| 天天干天天射天天日天天操| 日韩一二三区中文字幕在线视频精品| 亚洲91精品视频在线观看| 成人H动漫精品一区二区| 日韩精品一区二区三区高清免费| 91香蕉频蕉app下载| 欧美激情国产精品视频一区| 人妻熟女的高跟丝袜艳遇| 亚洲高清日韩中文字幕| 91狠狠人妻久久久久久综合| 豆国产98在线观看亚洲| 亚洲国产精品尤物yw在线| 亚洲中文av中文字幕在线| 欧美激情a成人综合亚洲综合| 国产精品日本一区二区在线看| 亚洲欧美日韩在线三区| 麻豆理论片在线观看| 精品天堂色吊丝一区二区| 神马午夜久久久久久| 国产精品久久久久久久久久一区|